Description
Store at: 0 to +50 °C
Install at: 0 to +50 °C, Bend minimum: 10 times V.D.
Operate at: -20 to +70 °C, Bend minimum: 15 times V.D.
Standard of reference
EN 50228-7, EN 50290-2-29, IEC 60228, IEC 60332-1-2, IEC 60754-1&2, IEC 61034-1
Design
Conductor material: Bare copper stranded conductors acc. to IEC 60228 class 2
Insulation: XLPE (2X) compound – TS EN 50290-2-29
Core identification:
– pairs: Black, White (Each numbered)
– triples: Black, White, Red (Each numbered)
Pairing: Cores twisted to form a pairs/triples, PES tape wrapped
Individual screening: Aluminium Foil in contact with Tinned copper solid drain wire 0,60 mm
Stranding (Laid up): individually screened pairs/triples stranded in layers, PES tape wrapped
Overall screening: Aluminium Foil in contact with Tinned copper drain wire 0,50 mm2 (7×0,30 mm)
Outer Sheath: LSZH (HFFR) compound – EN 50290-2-27
Outer sheath colour: Black, Blue , Grey RAL7001 (or on request)
Marking: APS Finland – ww/yy – RE-2X(st)H PiMF HFFR P/T count – 500V +70°C – EN50288-7 IEC60332-1-2 – P/N – lot# + meter
Environmental properties and Fire Performances
Flame retardant: IEC 60332-1, VDE 0482-332-1-2, BS EN 60332-1-2
Amount of halogen acid gas: IEC 60754-1, EN 50267-1
Degree of acidity of gases: IEC 60754-2, EN 50267-2
Smoke density test: IEC 61034-1, VDE 0482-1034-1/2
Electrical characteristics
Max conductor temperature: +90 °C
Rated Voltage: 500 V
Test voltage: 2,0 kV AC 1 min.
Insulation resistance: min. 1000 MΩ.km
Capacitance (nF/km) : max. 150 nF/km
Cross section (mm2) 0.50 0.75 1.0 1.3 1.5 2.5
Conductor IEC 60228 class 2 7x0,30 7x0,37 7x0,43 7x0,50 7x0,52 7x0,67
Conductor resistance max.(Ω/km) 36.0 24.5 18.1 14.5 12.1 7.41
Insulation thickness min.(mm) 0.44 0.44 0.44 0.44 0.44 .53
Insulation thickness nom.(mm) 0.60 0.6 0.6 0.6 0.6 0.7
L/R Ratio (µH/Ω) 25 25 25 40 40 60
Ordering and delivery information
Cable type | Product code | Copper weight (kg/km) | Outer diameter (mm) | Approx. weight (kg/km) |
---|---|---|---|---|
1x2x0.75 | RE2XSTHP | 18.6 | 6,9 | 57 |
2x2x0.75 | RE2XSTHP | 37.9 | 12.0 | 140 |
4x2x0.75 | RE2XSTHP | 71.5 | 14.1 | 210 |
6x2x0.75 | RE2XSTHP | 104.8 | 17.3 | 330 |
8x2x0.75 | RE2XSTHP | 138.4 | 19.6 | 390 |
10x2x0.75 | RE2XSTHP | 171.8 | 22.3 | 470 |
2x2x1.0 | RE2XSTHP | 47.8 | 12.5 | 160 |
5x2x1.0 | RE2XSTHP | 112.8 | 16.0 | 300 |
12x2x1.0 | RE2XSTHP | 164.6 | 24.5 | 630 |
20x2x1.0 | RE2XSTHP | 554.6 | 30.5 | 1050 |
1x2x1.5 | RE2XSTHP | 31.8 | 8.0 | 75 |
2x2x1.5 | RE2XSTHP | 64.8 | 13.7 | 195 |
4x2x1.5 | RE2XSTHP | 125.0 | 16.5 | 300 |
10x2x1.5 | RE2XSTHP | 305.7 | 25.0 | 730 |
12x2x1.5 | RE2XSTHP | 365.9 | 26.7 | 790 |
12x2x2.5 | RE2XSTHP | 593.3 | 33.0 | 1160 |
Every effort has been put so that this document is most reliable and free from errors. However, APS Cables & Connectors Oy cannot be considered responsible for any mistake in this document and users should consult APS Cables & Connectors Oy for any information needed. APS Cables & Connectors Oy reserves the right to make changes to the documents at any time, without prior notice.