Description
Installation features
Store at : -40 to +70°C
Install at : -5 to +50°C, Bend minimum : 20 times O.D.
Operate at : -40 to +85°C, Bend minimum : 15 times O.D.
Design
Bare fiber : 250µm
Buffer : Loose tube (Ø2.8mm up to 12 fibers, Ø3.5mm for 16-24 fibers) filled with jelly, housing up to 24 fibers
Fire barrier : mica tape.
Protection : anti-rodent glass yarns, water blocking.
Armour: corrugated steel tape.
Outer sheath : black fire retardant, UV-resistant and MUD-resistant LSZH SHF2 material (nom. thick. ≥1.0mm).
Marking : APS Finland ww/mm – FIBER OPTIC CABLE UTX92U [fibre count and type] – SHF2-MUD NEK606 – IEC60331-25 IEC60332-3-24 – Lot no + meter
Environmental properties and Fire Performances
Degree of acidity of gases : IEC 60754-1, IEC 60754-2 (pH value ≥ 4,3 and Conductivity ≤10µS/mm)
Halogen acid gas : IEC 60754-1, IEC 60754-2 (Halogen acid gas emission ≤ 0.5%)
Smoke Emission : IEC 61034-2, EN 50268-2 (Transmittance) ≥ 60%)
Toxicity of evolved gas : EN50305 9.2
Flame retardant : IEC 60332-1-2
Fire retardant : IEC 60332-3-24 Cat.C
Fire resistant : IEC 60331-25 (90 min.)
Ozone resistant : IEC60811-2-1, DIN VDE 0472 part 805 B
Weather resistant : ASTM G 154, EN 11507
Oil resistant : IEC60811, IRM 903
MUD resistant : NEK606:2009, IEC60092-350
Water absorption : IEC60811-1-3
Water penetration : IEC 60794-1-2-F5-B (inner core only)
UV resistant : ASTM G 154 IEC 60068-2-5
Mechanical properties
Pulling tension : 1500 N (Δα reversible, IEC 60794-1-2-E1)
Crush : 1000N/100mm (Δα reversible, IEC 60794-1-2-E3)
Impact : 5J (Δα reversible, IEC 60794-1-2-E4)
Water penetration : 3m cable, 1m water, 24 hours (IEC 60794-1-2-F5)
Colour code of fibers
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 |
Blue | Orange | Green | Brown | Grey | White | Red | Black | Yellow | Violet | Pink | Aqua |
13 | 14 | 15 | 16 | 17 | 18 | 19 | 20 | 21 | 22 | 23 | 24 |
Blue/b. | Orange/b. | Green/b. | Brown/b. | Grey/b. | White/b. | Red/b. | Natural | Yellow/b. | Violet/b. | Pink/b. | Aqua/b. |
Fiber Optic characteristics
See detailed specification of optical fibers.
Ordering and delivery information
Fiber Count | Part Number | No. of tubes | Fibers per tube | Nominal O.D. (mm) | Weight (kg/km) | Packaging |
---|---|---|---|---|---|---|
2 | UTX92U02 ff D2 | 1 | 2 | 9.5 | 120 | Drum 2000m +/-5% |
4 | UTX92U04 ff D2 | 1 | 4 | 9.5 | 120 | Drum 2000m +/-5% |
8 | UTX92U08 ff D2 | 1 | 8 | 9.5 | 120 | Drum 2000m +/-5% |
12 | UTX92U12 ff D2 | 1 | 12 | 9.5 | 120 | Drum 2000m +/-5% |
24 | UTX92U24 ff D2 | 1 | 24 | 9.5 | 120 | Drum 2000m +/-5% |
ff = S2 for G652D, A1 for G657A1, M1 for OM1, M2 for OM2, M3 for OM3, M4 for OM4, M5 for OM5. |
Recommended connectivity
Pigtails : APS LIIN-25 series
Patch cords : APS LIIN-25 series
Adapters : APS LIIN-25 series