Description
Features
- Fiber-count 12 and 24 fibers
- Over-jacketed for increased protection
- Bend-insensitive/bend optimized fibers
- Plenum (OFNP / FT6), LSZH Riser OFNR (FT-4-ST1)
- OS2, OM3 and OM4 performance types
- Colored outer-jacket to denote performance
- Ultra-low loss connector performance
- Suitable for routing in trays, racks and under raised floors
- Colored jacket for easy identification
- Compact 3mm strands for easy routing within racks and panels
Single-stranded trunks provide the backbone connection between patch panels in the data center. Single stranded trunks offer a high degree of flexibility and scalability and APS offer these with a secondary jacket to give a higher degree of protection within cable path ways.
Single-stranded trunks provide a scalable solution for users who wish to deploy just 12 or 24 fibers in a single cable rather than high fiber-count multi-stranded cables. This bite-sized approach makes it easier to redeploy cables if necessary and it helps to spread the costs of periodical installations.
With this cable construction, you get the best of both worlds because the cable is robust and protected in the pathways yet compact and flexible inside racks and in front of equipment. APS recommends that trunk cables are configured with male connectors at each end and polarity type B. This simplifies the upgrade path to higher data rates such as 40G and 100G.
Specifications
Mechanical data | 12 | 24 | |
Design | mm | 1 x 12 bare fiber | 1 x 24 bare fiber |
Sub-unit nominal diameter | mm | 2.9mm ±0.2 | 3.6mm ±0.2 |
Outer cable nominal diameter | mm | 4.5mm ±0.2 | 5.6mm ±0.2 |
Max installation tension | N | 440 | 440 |
Max. operation tension | N | 132 | 132 |
Min. bending radius without tension | mm | 10 x cable Ø | 10 x cable Ø |
Min. bending radius under max. tension | 0C | 20 x cable Ø | 20 x cable Ø |
Optical data | |
Fiber category | OS2 – 9/125 bend insensitive OM3/4 bend-optimized |
Trunk IL (LL/Low Loss) | Single mode OS2 ≤1.5dB Multimode OM3/OM4 ≤0.70dB |
Trunk IL (ULL/Ultra Low Loss) | Single mode OS2 ≤0.70dB Multimode OM3/OM4 ≤0.50dB |
Trunk RL (Return Loss) | Singlemode OS2 UPC ≥ 50dB Singlemode OS2 APC ≥ 60dB Multimode OM3/OM4 ≥ 30dB |
Environmental data
Description | |
Installation | LSZH (-10°C to +60°C), PLENUM (0°C to +60°C) |
Transport and storage | – 40°C to +70°C |
Operating temperature | -10°C to +70°C |
Free of halogen | Yes |
2011/65/EC RoHS | Fully compliant |
Ordering information
Example | STOO | 46 | M | 46 | L | B | 100 | 4 | 750 | 4 | 030M |
---|---|---|---|---|---|---|---|---|---|---|---|
Character | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 |
Extended System Warranty
The APS System Warranty assures the compliance of the system performance to the applicable class of cabling for a period of 25 years. The warranty may be applied for by an accredited APS Partner who has designed and/or installed the entire system. Learn about APS System Warranty from here.
Every effort has been put so that this document is most reliable and free from errors. However, AP Solutions Oy cannot be considered responsible for any mistake in this document and users should consult AP Solutions Oy for any information needed. AP Solutions Oy reserves the right to make changes to the documents at any time, without prior notice.