MOG Shielded Power DC Cable 2 Conductors (300M)

EMC screened, HF, Fire Retardant, sunlight resistant.
O492322, 28.02.2018/AP rev.0
Type Approval: – 

 

Print or Download PDF

Description

   

 

Store at: -20 to +50 °C
Install at: 0 to +50 °CBend minimum: 10 times O.D.
Operate at: -40 to +90 °CBend minimum: 10 times O.D.

Design

Conductor material:  stranded annealed tinned copper, Class 5 (IEC 60228). Three parallel cores to form a flat conductor.
Insulation :  Flame retardant polyolefin.
Cable core :  2 conductors
Colour code :  1.Grey, 2 90C.Black

Outer shield :  AL/PE laminate with braid of annealed tinned copper wires.
Outer Sheath :  Black Flame retardant polyethylene
Marking :  APS Finland – ww/yy – DC CABLE 2xAWG… 600V – HF IEC60332-3-24 Cat.C – lot – meter marking

 

Environmental properties and Fire Performances

Flame retardant :  IEC 60332-1-2
Fire retardant :  IEC 60332-3-24 Cat.C, UL 1685, Vertical Tray
UV resistant : ASTM-D-2565-92A, UL

 

Electrical characteristics

Max operating Voltage : 600V

 

Ordering and delivery information

TypeP/NDC Resistance (Ω/km)Nom. O.D [mm]
Nom. weight [kg/km]Packaging
2 x 2.5 (2x14AWG)O49232237.987.7 x 7.790500m (+/-5%)
2 x 4 (2x12AWG)O49232334.958.6 x 8.6125500m (+/-5%)
2 x 6 (2x10AWG)O49232433.309.4 x 9.4160500m (+/-5%)
2 x 10 (2x8AWG)O49232531.9110.7 x 10.7239500m (+/-5%)
2 x 16 (2x6AWG)O49232631.2112.5 x 12.5345500m (+/-5%)

 

 

Other standards of reference

TFL49232_

 

 

 

 

Every effort has been put so that this document is most reliable and free from errors. However, AP Solutions Oy cannot be considered responsible for any mistake in this document and users should consult AP Solutions Oy for any information needed. AP Solutions Oy reserves the right to make changes to the documents at any time, without prior notice.

 

 

 