Description
Store at: -20 to +70 °C
Install at: -5 to +65 °C, Bend minimum: 15 times O.D.
Operate at: -20 to +80 °C, Bend minimum: 20 times O.D.
Pull maximum: 150N
Design
Conductor : stranded plain annealed copper 0.35mm2
Insulation : foam polyethylene (PEE)
1 pair : 2 insulated conductors stranded together into a pair
2 pairs: 4 insulated conductors stranded together into a starquad
Colour code : 1.Green/red 2.Blue/brown
Wrapping : PET
Screen : PET/Al + DW + tinned copper wire braid ( + PET wrapping where needed) 0.35 mm2 (22 AWG) tinned copper drain wire
Inner jacket : Black or purple LSZH thermoplastic compound
Armour : galvanized steel wire armour (SWA)
Outer jacket : Black or purple LSZH thermoplastic compound
Marking : APS Finland – ww/yy – ARMOURED PROFIBUS …x2x0.35mm2 LSZH UVR – IEC60332-3-22 Cat.C – P/N + lot + meter
Electrical characteristics
Voltagerating: 300V
Dielectric test (core/core): 1000V a.c. for 1 min.
Dielectric test (core/screen): 500V a.c. for 1 min.
Conductor resistance @ 20°C: ≤ 55.0 Ω/km
Insulation resistance @ 20°C: ≥ 1GΩxkm
Nominal capacitance @ 800Hz: 34 nF/km @ 1MHz
Characteristic impedance: 150 Ω ± 15 @ 1MHz
Environmental properties and Fire Performances
Acid gas emission: IEC 60754-1 (HCl <= 0.5%)
Smoke Emission : IEC 61034-2 (transmittance >= 60%)
Flame retardant : IEC 60332-1-2
Fire retardant : IEC 60332-3-24 Cat. C
Ordering and delivery information
Pair count | P/N | Inner jacket O.D. [mm] | O.D [mm] | Weight [kg/km] | Packaging |
---|---|---|---|---|---|
1 pair (violet) | OPB1P035FHAH | 8.4 | 13.2 | 330 | 500 m (+/-5%) |
1 pair (black) | OPB2P035FHAH | 8.4 | 13.2 | 330 | 500 m (+/-5%) |
2 pairs (violet) | OPB1P035FHAHB | 8.4 | 13.2 | 330 | 500 m (+/-5%) |
2 pairs (black) | OPB2P035FHAHB | 8.4 | 13.2 | 330 | 500 m (+/-5%) |
Other standards of reference
IEC 60092-370 | Electrical installations in ships: Guidance on the selection of cables for telecommunication and data. |
IEC 60092-360 | Electrical installations in ships: Insulating and sheating materials for shipboard and offshore units. |
DNV TAP 827.50/2 | Type Approval Program |
ABS SVR | Rules for building and classing. Steel Vessels. |
ABS SMR | Rules for building and classing. Steel vessels under 90 meters. |
IEC 60811 | Insulating and sheathing materials of electric cables - Test method |
Every effort has been put so that this document is most reliable and free from errors. However, AP Solutions Oy cannot be considered responsible for any mistake in this document and users should consult AP Solutions Oy for any information needed. AP Solutions Oy reserves the right to make changes to the documents at any time, without prior notice.