MOG Profibus DP 1&2 pairs, Fire Retardant, Armoured, LSZH

Metal armoured, EMC screened, stranded conductor, LSZH, Fire Retardant IEC60332-3-24
OPB_P035FHAH, 25.09.2021/AP rev.00
Type Approval: –

 

 

 

Print or Download PDF

Description

    

 

 

Store at: -20 to +70 °C
Install at: -5 to +65 °CBend minimum: 15 times O.D.
Operate at: -20 to +80 °CBend minimum: 20 times O.D.
Pull maximum: 150N

 

 

Design

Conductor : stranded plain annealed copper 0.35mm2
Insulation : foam polyethylene (PEE)
1 pair : 2 insulated conductors stranded together into a pair
2 pairs: 4 insulated conductors stranded together into a starquad
Colour code : 1.Green/red   2.Blue/brown
Wrapping : PET
Screen : PET/Al + DW + tinned copper wire braid ( + PET wrapping where needed) 0.35 mm2 (22 AWG) tinned copper drain wire
Inner jacket : Black or purple LSZH thermoplastic compound
Armour : galvanized steel wire armour (SWA)
Outer jacket : Black or purple LSZH thermoplastic compound 
Marking : APS Finland – ww/yy – ARMOURED PROFIBUS …x2x0.35mm2 LSZH UVR – IEC60332-3-22 Cat.C – P/N + lot + meter

 

Electrical characteristics 

Voltagerating:  300V
Dielectric test (core/core):  1000V a.c. for 1 min.
Dielectric test (core/screen):  500V a.c. for 1 min. 
Conductor resistance @ 20°C:  ≤ 55.0 Ω/km
Insulation resistance @ 20°C:  ≥ 1GΩxkm
Nominal capacitance @ 800Hz:  34 nF/km @ 1MHz
Characteristic impedance:  150 Ω ± 15 @ 1MHz

 

 

Environmental properties and Fire Performances

Acid gas emission: IEC 60754-1 (HCl <= 0.5%)
Smoke Emission : IEC 61034-2 (transmittance >= 60%)
Flame retardant : IEC 60332-1-2
Fire retardant : IEC 60332-3-24 Cat. C

 

 

Ordering and delivery information

Pair countP/NInner jacket O.D. [mm]O.D [mm]Weight [kg/km]Packaging
1 pair (violet)OPB1P035FHAH8.413.2330500 m (+/-5%)
1 pair (black)OPB2P035FHAH8.413.2330500 m (+/-5%)
2 pairs (violet)OPB1P035FHAHB8.413.2330500 m (+/-5%)
2 pairs (black)OPB2P035FHAHB8.413.2330500 m (+/-5%)

 

 

 

Other standards of reference

IEC 60092-370 Electrical installations in ships: Guidance on the selection of cables for telecommunication and data.
IEC 60092-360Electrical installations in ships: Insulating and sheating materials for shipboard and offshore units. 
DNV TAP 827.50/2Type Approval Program
ABS SVRRules for building and classing. Steel Vessels.
ABS SMRRules for building and classing. Steel vessels under 90 meters.
IEC 60811Insulating and sheathing materials of electric cables - Test method

 

 

 

Every effort has been put so that this document is most reliable and free from errors. However, AP Solutions Oy cannot be considered responsible for any mistake in this document and users should consult AP Solutions Oy for any information needed. AP Solutions Oy reserves the right to make changes to the documents at any time, without prior notice.

 

 

 

SKU: OPB_P035FHAH Categories: , ,