Description
Standards of reference
Voltage rating
0.6/1 (1.2)kV
Temperature range
Maximum operating temperature: +90ºC
Maximum conductor temperature during S.C: +250ºC
Minimum bending radius
15 x Overall Diameter
Design
Conductor : Class 2 Stranded Plain Aluminium Circular Compacted Conductor
Insulation : XLPE (Cross linked Polyethylene) 90 degrees C
Bedding: PVC (Polyvinyl Chloride)
Armouring: AWA (Aluminium Wires)
Outer sheath: PVC (Polyvinyl Chloride), black
Marking : tba
Electrical characteristics
NOMINAL CROSS SECTIONAL AREA(mm2) | MAXIMUM CONDUCTOR DC RESISTANCE AT 20OC (Ω/Km) | MAXIMUM CONDUCTOR AC RESISTANCE AT 50 Hz (Ω/Km) | CONDUCTOR S.C.C (For 1 second KA) | CURRENT RATING (Laid in free air) |
---|---|---|---|---|
300 | 0.1 | 0.13 | 28.3 | 564 |
500 | 0.0605 | 0.085 | 47.2 | 757 |
Delivery information
Part number | Cores count | Conductor size mm²) | Nominal outer diameter (mm) | Nominal cable weight (kg/km) | Delivery length (m) |
---|---|---|---|---|---|
ALXVAV61300 | 1 | 300 | 33.0 | 1600 | tba |
ALXVAV61500 | 1 | 500 | 41.5 | 2550 | tba |
Every effort has been put so that this document is most reliable and free from errors. However, APS Cables & Connectors Oy cannot be considered responsible for any mistake in this document and users should consult APS Cables & Connectors Oy for any information needed. APS Cables & Connectors Oy reserves the right to make changes to the documents at any time, without prior notice.