Description
Store at: 0 to +50 °C
Install at: 0 to +50 °C, Bend minimum: 10 times V.D.
Operate at: -30 to +90 °C, Bend minimum: 15 times V.D.
Standard of reference
IEC 60228, IEC 60332-1-2
Design
Conductor material: Bare stranded copper wire class 2 – 7×2,00 mm (4 AWG)
Insulation: XLPE (2X) compound
Core identification: black, blue
Insulation thickness: nom. 0,90 mm
insulation diameter: nom. 7,80 mm
Stranding (lay up): Cores stranded
Inner sheath : PVC compound
Screening over inner sheath: Aluminium Foil + 7×1,0 mm (10 AWG -5,49 mm2) Tinned copper stranded drain wire
Outer sheath: PVC compound Oil/UV Res.
Marking: APS Finland – ww/yy – 2 x 4AWG – 0.6/1kV +90°C – IEC60332-1-2 – P/N – lot# + meter
Environmental properties and Fire Performances
Flame retardant: IEC 60332-1
Electrical characteristics
Rated Voltage: 600/1000 V
Test voltage: 3,5 kV AC 1 min.
Insulation resistance: min. 1000 MΩ.km
Conductor DC Resistance: max. 0,91 Ω/km
Ordering and delivery information
Product no: F2XRSTR2400
Copper weight: 464.6 kg/km
Overall diameter: 25.5 +/- 1.5 mm
Net weight: 1100 kg/km (nominal)
Every effort has been put so that this document is most reliable and free from errors. However, APS Cables & Connectors Oy cannot be considered responsible for any mistake in this document and users should consult APS Cables & Connectors Oy for any information needed. APS Cables & Connectors Oy reserves the right to make changes to the documents at any time, without prior notice.