CCTV Composite cable Fire Retardant, Data + Power, Metallic Armoured, LSZH

DATA 4P CATEGORY 6A, POWER 3×2.5mm², LSZH, Fire Retardant, metallic armoured.
OC6A4PFU325H Rev.00, Date 2018-04-19

 

Print or Download PDF

Description

      

Standards of reference

IEC 60092-370Electrical installations in ships: Guidance on the selection of cables for telecommunication and data.
IEC 60092-360 Electrical installations in ships: Insulating and sheating materials for shipboard and offshore units.
CEI EN 50289 Communication cables - Specifications for test methods
EN 50290-2-23 Insulation materials for telecommunication cables
IEC 60811 Insulating and sheathing materials of electric cables - Test method
IEC 60793General specifications for both multimode and single-mode optical fibres
IEC 60794General specifications for optical fibre cables

 

 

 

Installation Features

Store at  -10 to +70 °C
Install at  -6 to +50 °C, bend minimum 15 times O.D.
Operate at : -30 to +80 °C, bend minimum : 20 times O.D.
Pull maximum : 350N

 

Design

Category 6A, 4 pairs
Conductor
:  plain annealed copper wire, solid, nominal Ø 0.56mm

Insulation :  SFS polyethylene, nominal Ø 1.33mm
Colour code :  white/blue, white/orange, white/green, white/brown.
Screen : collective aluminium/mylar tape, 100% coverage with tinned copper drain wire
Sheath : blue non-corrosive thermoplastic compound, LSZH, nominal Ø 7.5mm

Power 3 conductors 2.5mm²
Conductor :  plain annealed copper wire, 7 strands, 2.5mm2
Insulation :  XLPE, nominal Ø 3.5mm, colour coded (1.Brown, 2.Black, 3.Grey)
DC resistance per core @ 20°C :  ≤ 7.6 Ω/km
Insulation resistance @ 20°C :  ≥ 5000 MΩ x km
Mutual capacitance :  max 150 nF/km
Inductance :  max 1 mH/km
Test Voltage core/core :  5000 V
Test Voltage core/screen :  2000 V
Operating Voltage :  600/1000V 

Assembling
Cable core : 1 Category 6A element and 3 power conductors stranded together into a compact core, with fillers and wrapping where necessary.

Inner jacket :  LSZH thermoplastic compound, Ø 12.7mm, black colour
Armour :  Galvanized Steel Wire Braid, coverage ≥ 80% (alternatively concentric steel or stainless steel wire, or bronze braid)
Outer jacket :  LSZH thermoplastic compound, Ø 17.7mm, black colour

Marking : APS Finland – ww/yy  –  CCTV COMPOSITE CABLE DATA Category 6A 4P +  POWER 3×2.5mm²  –  P/N  –  LSZH  IEC60502  IEC60332-3 –  lot + m 

 

Environmental properties and Fire Performances

Degree of acidity of gases :  IEC 60754-1, IEC 60754-2 
Halogen acid gas :  IEC 60754-1, IEC 60754-2 (Halogen acid gas emission ≤ 0.5%)
Smoke Emission :  IEC 61034-2, EN 50268-2 (Transmittance ≥ 60%)
Toxicity of evolved gas :  EN50305 9.2
Flame retardant :  IEC 60332-1-2
Fire retardant :  IEC 60332-3
UV retardant :  UL 1581 sect. 1200 

 

Ordering and delivery information

Cable typeP/NO.D [mm]Weight [kg/km]Packaging
UnarmouredOC6A4PFU325H12.7390drum 500m (+/-5%)
Armoured GSWBOC6A4PFU325FH17.5500drum 500m (+/-5%)
Armoured GSWAOC6A4PFU325AH17.7543drum 500m (+/-5%)
Armoured Bronze braidOC6A4PFU325BH17.5500drum 500m (+/-5%)
Armoured St. Steel braidOC6A4PFU325SH18.5570drum 500m (+/-5%)

 

Every effort has been put so that this document is most reliable and free from errors. However, AP Solutions Oy cannot be considered responsible for any mistake in this document and users should consult AP Solutions Oy for any information needed. AP Solutions Oy reserves the right to make changes to the documents at any time, without prior notice.

SKU: OC4xx2P24325H-1 Categories: , ,