Description
Store at : -20 to +70 °C
Install at : -20 to +70 °C, Bend minimum : 20 times O.D.
Operate at : -65 to +80 °C, Bend minimum : 20 times O.D.
Pull maximum : 50N
Design
Conductor : stranded tinned copper 7×0.20mm AWG24 (0.60mm, 0.22mm2)
Insulation : polyethylene Ø1.30mm
Pair : 2 insulated conductors stranded together into a pair
Colour code : 1.White/blue 2.White/orange 3. White/green 4.White/brown
Assembling : 1, 2 or 4 pairs assembled together into a compact core
Overall screen 1 : aluminium/polyester tape (coverage 100%) with stranded tinned copper drain wire 7×0.20mm.
Overall screen 2 : tinned copper braid (nominal coverage 85%)
Inner jacket : black Fire Retardant SHF1 material, LSZH (Ø 8.0mm)
Armour : galvanized steel wires, tinned copper or bronze wires braid (nominal coverage 85%)
Outer jacket : black Fire Retardant and UV Resistant SHF2 material, LSZH (nominal thickness 1.5mm)
Marking : APS Finland – ww/yy – ARCTIC GRADE RS485 SHF2 ARMOURED CABLE … PAIRS 24AWG 100 OHM – IEC60332-3-22 Cat A – lot + m
Environmental properties and Fire Performances
Degree of acidity of gases : IEC 60754-1, IEC 60754-2 (pH value ≥ 4,3 and Conductivity ≤10µS/mm)
Halogen acid gas : IEC 60754-1, IEC 60754-2 (Halogen acid gas emission ≤ 0.5%)
Smoke Emission : IEC 61034-2, EN 50268-2 (Transmittance) ≥ 60%)
Toxicity of evolved gas : EN 50305 9.2
Flame retardant : IEC 60332-1-2
Fire retardant : IEC 60332-3-22 Cat.A
Ozone resistant : IEC 60811-2-1
LSZH SHF2 : IEC 60092-360
Oil resistant : IEC 60811, IRM 903
MUD resistant : upon request
Water absorption : IEC60811-1-3
UV resistant : IEC60811-2-1, ASTM-D-2565-92A
Cold Bend : CSA C22.2 (-65°C)
Cold Impact : CSA C22.2 (-55°C)
Electrical characteristics
Operation voltage : 100V
Test voltage : 2000V d.c. for 1 minute
Resistance of the conductor @ 20°C : ≤ 90 Ω/km
Insulation resistance @ 20°C : ≥ 1GΩxkm
Nominal Capacitance @ 800Hz : 42 pF/m
Characteristic impedance : 120 ± 15 Ω @ 1MHz
Nominal attenuation : 22 dB/km @ 1MHz
Ordering and delivery information
Pair count | P/N | O.D [mm] | Weight [kg/km] | Packaging |
---|---|---|---|---|
1 pair | ORS5A1P24Fx2 | 12.2 | 200 | drum 500m (+/-5%) |
2 pairs | ORS5A2P24Fx2 | 12.2 | 200 | drum 500m (+/-5%) |
4 pairs | ORS5A4P24Fx2 | 12.2 | 220 | drum 500m (+/-5%) |
For armour replace x with “A” for Galvanized Steel Wire Braid, “T” for Tinned Copper Wire Braid, “B” for Bronze Wire Braid.
Other standards of reference
IEC 60092-370 | Electrical installations in ships: Guidance on the selection of cables for telecommunication and data. |
IEC 60092-360 | Electrical installations in ships: Insulating and sheating materials for shipboard and offshore units. |
DNV TAP 827.50/2 | Type Approval Program |
ABS SVR | Rules for building and classing. Steel Vessels. |
ABS SMR | Rules for building and classing. Steel vessels under 90 meters. |
IEC 60811 | Insulating and sheathing materials of electric cables - Test method |
Every effort has been put so that this document is most reliable and free from errors. However, AP Solutions Oy cannot be considered responsible for any mistake in this document and users should consult AP Solutions Oy for any information needed.