Arctic Grade Profibus cable 1&2 pairs 0.35mm2 SHF2

EMC screened, stranded conductor -65°C, SHF2, Fire Retardant IEC60332-3-22 Cat.A
OPBA1P035F2/OPBA2P035F2, 01.03.2015/AP rev.0

 

Print or Download PDF

Description

 

    

 

Store at : -20 to +70 °C
Install at : -20 to +70 °CBend minimum : 20 times O.D.
Operate at : -65 to +80 °CBend minimum : 20 times O.D.
Pull maximum : 50N

Design

Conductor : Stranded bare copper 7×0.25 (0.35mm2 )
Insulation : Polyolefin Ø2.75mm
Pair : 2 insulated conductors stranded together into a pair
Colour code : 1.Green/red 2.Blue/brown
Assembling : No 1 pair with fillers or no 2 pairs stranded together into a compact core
Screen : Aluminium/polyester tape (100%) with tinned copper braid (coverage ≥60%)
Outer jacket : Black or purple Fire Retardant and UV Resistant SHF2 material, LSZH (Ø 9,6mm)
Marking : APS Finland – ww/yy – ARCTIC GRADE PROFIBUS MARINE …x2x0.35mm2 SHF2 – IEC60332-3-22 Cat.A – TK/lot + meter

Environmental properties and Fire Performances

Degree of acidity of gases : IEC 60754-1, IEC 60754-2 (pH value ≥ 4,3 and Conductivity ≤10µS/mm)
Halogen acid gas : IEC 60754-1, IEC 60754-2 (Halogen acid gas emission ≤ 0.5%)
Smoke Emission : IEC 61034-2, EN 50268-2 (Transmittance) ≥ 60%)
Toxicity of evolved gas : EN 50305 9.2
Flame retardant : IEC 60332-1-2
Fire retardant : IEC 60332-3-22 Cat.A
Ozone resistant : IEC 60811-2-1
LSZH SHF2 : IEC 60092-360
Oil resistant : IEC 60811, IRM 903
MUD resistant : upon request
Water absorption : IEC60811-1-3
UV resistant : IEC60811-2-1, ASTM-D-2565-92A
Cold Bend : CSA C22.2 (-65°C)
Cold Impact : CSA C22.2 (-55°C)

 

 

Electrical characteristics (IEC60092-350, IEC61784, IEC61158)

Operation voltage : 100V
Test voltage : 1500V a.c. for 1 minute
Resistance of the conductor @ 20°C : ≤ 55.0 Ω/km
Insulation resistance @ 20°C : ≥ 1GΩxkm
Nominal Capacitance @ 800Hz : 30 pF/m
Characteristic impedance : 150 Ω ± 15 @ 1MHz

Nominal attenuation :45 dB/km@ 16MHz
22 dB/km@ 4MHz
5 dB/km@ 38,4 KHz
3 dB/km@ 9,6 KHz
Baudrate :9.6 kBits/s@ Max. 1200m
19.2 kBits /@ Max. 1200m
93.75 kBits/s@ Max. 1200m
187.5 kBits /s @ Max. 1000m
500 kBits /s@ Max. 400m
1.5 MBits /s@ Max. 200m
12 MBits /s@ Max. 100m

 

Ordering and delivery information

  Pair count P/N O.D [mm] Weight [kg/km] Packaging 
1 pair OPBA1P035F2 9.6 95 drum 500m (+/-5%) 
2 pairs OPBA2P035F2 9.6 120 drum 500m (+/-5%) 

 

 

Other standards of reference

IEC 60092-370 Electrical installations in ships: Guidance on the selection of cables for telecommunication and data.
IEC 60092-360Electrical installations in ships: Insulating and sheating materials for shipboard and offshore units. 
DNV TAP 827.50/2Type Approval Program
ABS SVRRules for building and classing. Steel Vessels.
ABS SMRRules for building and classing. Steel vessels under 90 meters.
IEC 60811Insulating and sheathing materials of electric cables - Test method

 

 

 

 

 